BEST PRACTICES – MSE WALL BACKFILL RECOMMENDATIONS
- Home
- News
- BEST PRACTICES – MSE WALL BACKFILL RECOMMENDATIONS
BEST PRACTICES – MSE WALL BACKFILL RECOMMENDATIONS
For Walls Up To 10 Feet:
- Recommended Backfill Types = GW, GP, SW, SP, SM, SC
- Maximum Atterberg Limits (LL and PI) = PI < 20, LL <40
- Minimum Compaction = 95% of Standard Proctor Density
- Moisture Content = +/- 2% of optimum moisture
- Recommended Material Gradation:
SIEVE SIZE | PERCENT PASSING |
1 in. | 100 |
No. 4 | 20-100 |
No. 40 | 0-60 |
No. 200 | 0-35 |
For Walls 10 Feet to 20 Feet:
- Recommended Backfill Types = GW, GP, SW, SP, SM, SC
- Maximum Atterberg Limits (LL and PI) = PI < 6, LL <40
- Minimum Compaction = 98% of Standard Proctor Density
- Moisture Content = +/- 2% of optimum moisture
- Recommended Material Gradation = Same as walls shorter than 10 – feet
For Walls Over 20 Feet:
- Recommended Backfill Types = GW, GP, SW, SP
- Maximum Atterberg Limits (LL and PI) = PI < 6
- Minimum Compaction = 98% of Standard Proctor Density
- Moisture Content = +/- 2% of optimum moisture
- Recommended Material Gradation:
SIEVE SIZE | PERCENT PASSING |
1 in. | 100 |
No. 4 | 20-100 |
No. 40 | 0-60 |
No. 200 | 0-15 |