BEST PRACTICES – GEOGRID REINFORCEMENT

The National Concrete Masonry Association (NCMA) has put together a collection of  practical, field proven solutions.  This excerpt is for best practices when using geogrid reinforcement. 

Reinforcement Empirical Limits:

  • Minimum grid length =
    • 60% H static,
    • 60% bottom/middle and
    • 90% upper layers for seismic
  • Absolute minimum grid length = 4.00 feet
  • Minimum anchorage length (beyond failure plane) = 1 foot
  • Maximum vertical spacing =
    • 16 inches if % passing #200 is >35%
    • 24 inches if % passing #200 is <35%
  • Maximum vertical spacing = twice (2x) the block depth
  • Minimum soil cover between layers = 3 inches
  • Maximum height to first layer of geogrid = 18 inches

    For more information on best practices for segmental retaining walls, download the NCMA guide here.

    Read more

    NCMA & AASHTO WALL EMBEDMENT REQUIREMENTS

    Embedment Rules:

    1. Embed to a depth that provides 4-feet horizontal bench to daylight (i.e. For a 4H:1V slope, embed the toe of wall 1-foot minimum)
    2. AASHTO requires 24” minimum for slopes steeper than a 4H:1V
    3. AASHTO requires 24” minimum when the wall is in a water application with no permanent erosion prevention measures such as rip-rap or a hardened liner above grade.
    4. Embed toe of wall below curbing or other site components to be installed after wall construction.
    wall embedment chart
    Read more
    best practices MSE wall backfill

    BEST PRACTICES – MSE WALL BACKFILL RECOMMENDATIONS

    For Walls Up To 10 Feet:

    • Recommended Backfill Types = GW, GP, SW, SP, SM, SC
    • Maximum Atterberg Limits (LL and PI) = PI < 20, LL <40
    • Minimum Compaction = 95% of Standard Proctor Density
    • Moisture Content = +/- 2% of optimum moisture
    • Recommended Material Gradation:
    SIEVE SIZEPERCENT PASSING
    1 in.100
    No. 420-100
    No. 400-60
    No. 2000-35

    For Walls 10 Feet to 20 Feet:

    • Recommended Backfill Types = GW, GP, SW, SP, SM, SC
    • Maximum Atterberg Limits (LL and PI) = PI < 6, LL <40
    • Minimum Compaction = 98% of Standard Proctor Density
    • Moisture Content = +/- 2% of optimum moisture
    • Recommended Material Gradation = Same as walls shorter than 10 – feet

    For Walls Over 20 Feet:

    • Recommended Backfill Types = GW, GP, SW, SP
    • Maximum Atterberg Limits (LL and PI) = PI < 6
    • Minimum Compaction = 98% of Standard Proctor Density
    • Moisture Content = +/- 2% of optimum moisture
    • Recommended Material Gradation:
    SIEVE SIZEPERCENT PASSING
    1 in.100
    No. 420-100
    No. 400-60
    No. 2000-15
    Read more